Structure: |
Steel frame with concrete slabs and concrete fireproofing. |
Façade: |
Aluminum window system and gold tinted windows. |
Roof: |
Roof space is limited to mechanical structures. Racks
and additional equipment can be located on the 16th
floor Tower Data Center. |
Floor Loading: |
50 - 80 pounds per sq. ft. live load (can be reinforced
at column lines). |
Ceiling Heights: |
Slab to slab: 13 ft, to lowest beams: 9'-11" |
Column Distance: |
28 ft. x 28 to 32 ft. |
Electrical Capacity: |
Typical power allocation is approximately 40 watts
per sq. ft. expandable to 80 watts per sq. ft.
Each cabinet and 4' x 6' cage receives a 110 volt,
20 amp circuit. Main power is 480 volt, 3 phase. |
Elevators: |
Five passenger sevice elevator operate during regular
business hours. Two secure passenger elevators operate
during non-business hours. One frieght elevator with
a 3,500-pound capacity. |
Fire Suppression: |
Existing wet system can be converted to a pre-action
system. FM-200 system can be installed. Meet-Me Room
is a zoned pre-action system. |
Security: |
Manned, on-site security is present 24/7/365. Keycard
system is in place for after-hours building entry
and floor access. |
Risers: |
Riser space available for Telecommunication pathways
from diverse entries. Fully master-planned riser system,
providing diverse riser capacity for fiber, HVAC piping,
electric and fuel riser needs. |
Parking: |
Underground gated parking area, not open to public
access. |
Delivery Area Loading: |
A loading area in the surface lot at the south side
of the building is available to tenants for delivery
of equipment. |
Operating Engineers: |
On-site operating engineers to support building systems
and provide tenant service. |
Other Core Systems: |
On-site building engineers available for tenant service. |
Primary Power: |
Market Post Tower has 480 volt, 3-phase power delivered
to the central power riser on each floor via a conduit
riser system. Power allocated is based on the tenant's
actual demonstrated loads. Typical power allocation
is 80 watts per sq. ft.in suite 1070 and 1090 data
centers. |
Emergency Power: |
The Landlord has one 2000 KW generator, a 900 KW generator
and a 500 KW generator. Generator power is brought
to the power riser on each floor through a conduit
riser system. An additional 2000 KW generator will
be added as demand increases. |
Fuel Storage: |
Market Post Tower has existing fuel storage and containment
and associated pumping for 24 hours of continuous
generator use. |
HVAC
Cooling: |
The Landlord is installing a new, fully redundant,
1,500-ton condenser water system with tenant tap-ins
pre-installed in one of the wet risers on each floor.
|